Calculator Cfm

CFM Calculator: Calculate Cubic Feet per Minute for Ventilation :root { –primary-color: #004a99; –success-color: #28a745; –background-color: #f8f9fa; –text-color: #333; –label-color: #555; –border-color: #ccc; –shadow-color: rgba(0, 0, 0, 0.1); –white: #fff; } body { font-family: 'Segoe UI', Tahoma, Geneva, Verdana, sans-serif; background-color: var(–background-color); color: var(–text-color); line-height: 1.6; margin: 0; padding: 0; display: flex; justify-content: center; padding-top: 20px; padding-bottom: 40px; } .container { width: 100%; max-width: 960px; margin: 0 auto; padding: 20px; background-color: var(–white); border-radius: 8px; box-shadow: 0 4px 15px var(–shadow-color); } header { text-align: center; margin-bottom: 30px; padding-bottom: 20px; border-bottom: 1px solid var(–border-color); } h1 { color: var(–primary-color); margin-bottom: 10px; font-size: 2.5em; } .sub-heading { font-size: 1.2em; color: var(–label-color); } .calculator-section { margin-bottom: 40px; padding: 30px; background-color: var(–white); border-radius: 8px; box-shadow: 0 2px 10px var(–shadow-color); } .calculator-section h2 { color: var(–primary-color); text-align: center; margin-bottom: 25px; font-size: 2em; } .loan-calc-container { display: flex; flex-direction: column; gap: 20px; } .input-group { display: flex; flex-direction: column; margin-bottom: 15px; } .input-group label { display: block; margin-bottom: 8px; font-weight: bold; color: var(–label-color); font-size: 0.95em; } .input-group input[type="number"], .input-group select { width: 100%; padding: 12px 15px; border: 1px solid var(–border-color); border-radius: 5px; font-size: 1em; box-sizing: border-box; transition: border-color 0.3s ease; } .input-group input[type="number"]:focus, .input-group select:focus { border-color: var(–primary-color); outline: none; } .helper-text { font-size: 0.85em; color: var(–label-color); margin-top: 5px; } .error-message { color: #dc3545; font-size: 0.85em; margin-top: 5px; display: none; /* Hidden by default */ } .button-group { display: flex; gap: 10px; margin-top: 20px; } button { padding: 12px 25px; border: none; border-radius: 5px; cursor: pointer; font-size: 1em; font-weight: bold; transition: background-color 0.3s ease, transform 0.2s ease; } button.primary { background-color: var(–primary-color); color: var(–white); } button.primary:hover { background-color: #003366; transform: translateY(-2px); } button.secondary { background-color: #6c757d; color: var(–white); } button.secondary:hover { background-color: #5a6268; transform: translateY(-2px); } button.reset { background-color: #ffc107; color: #212529; } button.reset:hover { background-color: #e0a800; transform: translateY(-2px); } .results-container { margin-top: 30px; padding: 25px; border: 1px dashed var(–border-color); border-radius: 8px; background-color: #e9ecef; } .results-container h3 { color: var(–primary-color); margin-top: 0; text-align: center; margin-bottom: 20px; font-size: 1.8em; } .main-result { font-size: 2.5em; font-weight: bold; color: var(–success-color); text-align: center; margin-bottom: 20px; padding: 15px; background-color: #e0f2f7; border-radius: 5px; border: 1px solid var(–success-color); } .intermediate-results { display: grid; grid-template-columns: repeat(auto-fit, minmax(180px, 1fr)); gap: 15px; margin-bottom: 20px; text-align: center; } .intermediate-results div { background-color: var(–white); padding: 15px; border-radius: 5px; border: 1px solid var(–border-color); box-shadow: 0 1px 5px var(–shadow-color); } .intermediate-results span { display: block; font-size: 1.8em; font-weight: bold; color: var(–primary-color); } .intermediate-results p { font-size: 0.9em; margin: 0; color: var(–label-color); } .formula-explanation { font-size: 0.9em; color: var(–label-color); text-align: center; margin-top: 15px; padding-top: 15px; border-top: 1px solid var(–border-color); } .copy-button { display: block; width: fit-content; margin: 20px auto 0 auto; background-color: #17a2b8; color: var(–white); } .copy-button:hover { background-color: #138496; transform: translateY(-2px); } .chart-container { margin-top: 40px; padding: 30px; background-color: var(–white); border-radius: 8px; box-shadow: 0 2px 10px var(–shadow-color); text-align: center; } .chart-container h3 { color: var(–primary-color); margin-bottom: 20px; font-size: 2em; } canvas { max-width: 100%; height: auto !important; /* Ensure responsiveness */ } .chart-caption { font-size: 0.9em; color: var(–label-color); margin-top: 10px; } .table-container { margin-top: 40px; padding: 30px; background-color: var(–white); border-radius: 8px; box-shadow: 0 2px 10px var(–shadow-color); overflow-x: auto; /* For responsiveness */ } .table-container h3 { color: var(–primary-color); text-align: center; margin-bottom: 20px; font-size: 2em; } table { width: 100%; border-collapse: collapse; margin-top: 20px; } th, td { padding: 12px 15px; text-align: left; border: 1px solid var(–border-color); } thead th { background-color: var(–primary-color); color: var(–white); font-weight: bold; } tbody tr:nth-child(even) { background-color: #f2f2f2; } .article-content { margin-top: 40px; padding: 30px; background-color: var(–white); border-radius: 8px; box-shadow: 0 2px 10px var(–shadow-color); } .article-content h2, .article-content h3 { color: var(–primary-color); margin-top: 25px; margin-bottom: 15px; } .article-content h2 { font-size: 2.2em; } .article-content h3 { font-size: 1.7em; } .article-content p { margin-bottom: 15px; } .article-content ul, .article-content ol { margin-bottom: 15px; padding-left: 25px; } .article-content li { margin-bottom: 8px; } .article-content strong { color: var(–primary-color); } .article-content a { color: var(–primary-color); text-decoration: none; font-weight: bold; } .article-content a:hover { text-decoration: underline; } .variables-table td, .variables-table th { font-size: 0.95em; } .variables-table td:first-child { font-weight: bold; color: var(–primary-color); } .faq-section .faq-item { margin-bottom: 15px; padding: 15px; background-color: #e9ecef; border-radius: 5px; border: 1px solid #dee2e6; } .faq-section .faq-item .question { font-weight: bold; color: var(–primary-color); cursor: pointer; display: block; position: relative; padding-left: 25px; } .faq-section .faq-item .question::before { content: '+'; position: absolute; left: 5px; font-weight: bold; } .faq-section .faq-item.open .question::before { content: '-'; } .faq-section .faq-item .answer { display: none; margin-top: 10px; padding-left: 10px; } .related-tools-section ul { list-style: none; padding: 0; } .related-tools-section li { margin-bottom: 15px; padding: 10px; background-color: #e9ecef; border-radius: 5px; border: 1px solid #dee2e6; } .related-tools-section li a { font-weight: bold; } .related-tools-section li p { font-size: 0.9em; color: var(–label-color); margin-top: 5px; margin-bottom: 0; } /* Responsive adjustments */ @media (max-width: 768px) { h1 { font-size: 1.8em; } .sub-heading { font-size: 1em; } .calculator-section h2, .chart-container h3, .table-container h3, .article-content h2 { font-size: 1.8em; } .calculator-section { padding: 20px; } .results-container { padding: 20px; } .main-result { font-size: 2em; } .intermediate-results { grid-template-columns: 1fr; } .button-group { flex-direction: column; } button { width: 100%; } .container { padding: 15px; } canvas { max-width: 100%; } }

CFM Calculator: Calculate Cubic Feet per Minute

Your essential tool for determining airflow requirements for ventilation and HVAC systems.

Ventilation CFM Calculator

Enter the length of the room in feet.
Enter the width of the room in feet.
Enter the height of the room in feet.
How many times should the air be fully replaced each hour?

Your Ventilation Requirements

— CFM

Room Volume (cu ft)

Air Exchanges / Min

CFM Needed

Formula: CFM = (Room Volume in cu ft * Air Changes per Hour) / 60 minutes

CFM vs. Room Volume Impact

Visualizing how room volume affects required CFM for a fixed ACH.

CFM Recommendations by Room Type

Room Type Typical ACH Range Estimated CFM per 100 sq ft Example Application
Residential (General) 4-8 20-40 Living rooms, bedrooms
Kitchens (Residential) 10-20 50-100+ Cooking areas, range hoods
Bathrooms (Residential) 10-15 40-70 Exhausting moisture
Home Offices 6-12 30-50 Concentrated use areas
Commercial Spaces 5-15 25-60 Retail, small offices
Industrial/Labs 15-30+ 75-150+ Specialized ventilation

What is CFM (Cubic Feet per Minute)?

CFM stands for Cubic Feet per Minute. In the context of ventilation and HVAC (Heating, Ventilation, and Air Conditioning) systems, CFM is the standard unit of measurement used to quantify the volume of air moved by a fan or ventilation system per minute. Essentially, it tells you how much air your system can process and circulate within a given timeframe. Understanding CFM is crucial for designing effective ventilation systems that ensure adequate air quality, temperature control, and the removal of pollutants, moisture, or odors from a space.

Who should use it? Anyone involved in designing, installing, or maintaining ventilation systems will find CFM calculations essential. This includes HVAC professionals, building contractors, architects, home renovators, and even homeowners looking to improve their indoor air quality. Whether you're sizing a bathroom exhaust fan, a whole-house ventilation system, or a commercial HVAC unit, knowing the required CFM is a fundamental step.

Common misconceptions about CFM include:

  • Higher CFM is always better: Not necessarily. An excessively high CFM can lead to drafts, discomfort, increased energy consumption, and noise. The goal is to achieve the *right* CFM for the specific application, not the highest possible.
  • CFM is the only factor in ventilation effectiveness: While critical, CFM works in conjunction with other factors like ductwork design, air filtration, static pressure, and the type of fan or system used.
  • All fans move air equally: Fans vary significantly in their CFM ratings, static pressure capabilities, and energy efficiency. A fan rated for high CFM might not perform well in a system with long duct runs or restrictive filters.

CFM Formula and Mathematical Explanation

The most common method for calculating the required CFM for a space, especially for general ventilation and air quality purposes, is based on the room's volume and the desired rate of air exchange. This is often referred to as the ACH (Air Changes per Hour) method.

The core idea is to determine how many times the entire volume of air within a room needs to be replaced or recirculated each hour to maintain desired air quality.

The Formula:

The calculation proceeds in a few steps:

  1. Calculate Room Volume: This is the total cubic footage of the space.
  2. Determine Air Changes per Hour (ACH): This is a crucial factor based on the room's intended use and occupancy.
  3. Convert ACH to Air Exchanges per Minute: Since CFM is a rate per minute, we divide ACH by 60.
  4. Calculate Required CFM: Multiply the room volume by the air exchanges per minute.

Mathematically, this is expressed as:

Step 1: Room Volume (cu ft) = Length (ft) × Width (ft) × Height (ft)

Step 2: Air Exchanges per Minute = Air Changes per Hour (ACH) / 60

Step 3: Required CFM = Room Volume (cu ft) × Air Exchanges per Minute

Or, combining these:

CFM = (Length × Width × Height × ACH) / 60

Variable Explanations:

Here's a breakdown of the variables involved in the CFM calculation:

Variable Meaning Unit Typical Range/Notes
Length The longest dimension of the room. Feet (ft) Measure from wall to wall.
Width The shorter horizontal dimension of the room. Feet (ft) Measure from wall to wall.
Height The vertical dimension of the room from floor to ceiling. Feet (ft) Standard ceiling heights are often 8-10 ft.
Room Volume The total cubic space within the room. Cubic Feet (cu ft) Calculated value.
ACH Air Changes per Hour; how many times the total air volume is replaced per hour. Per Hour Varies by room use (e.g., 4-12 for residential, 10-20+ for kitchens/baths, higher for commercial/industrial).
Air Exchanges per Minute The rate at which air is replaced each minute. Per Minute Derived from ACH (ACH / 60).
CFM Cubic Feet per Minute; the volume of air moved per minute. Cubic Feet per Minute (CFM) The final calculated airflow requirement.

Practical Examples (Real-World Use Cases)

Let's illustrate the CFM calculation with two practical scenarios:

Example 1: Calculating CFM for a Residential Bathroom

Consider a typical residential bathroom measuring 8 feet long, 6 feet wide, and 8 feet high. The goal is to effectively remove moisture and odors, so a higher ACH is desired.

  • Inputs:
    • Room Length: 8 ft
    • Room Width: 6 ft
    • Room Height: 8 ft
    • Desired ACH: 15 (typical for bathrooms)
  • Calculations:
    • Room Volume = 8 ft × 6 ft × 8 ft = 384 cu ft
    • Air Exchanges per Minute = 15 ACH / 60 = 0.25 per minute
    • Required CFM = 384 cu ft × 0.25 per minute = 96 CFM
  • Result: You would need an exhaust fan rated for at least 96 CFM for this bathroom to ensure adequate ventilation. This helps prevent mold and mildew growth and quickly removes unpleasant odors.

Example 2: Calculating CFM for a Home Office

Now, let's calculate the CFM for a home office that is 12 feet long, 10 feet wide, and 9 feet high. This space is used for focused work, requiring good air quality.

  • Inputs:
    • Room Length: 12 ft
    • Room Width: 10 ft
    • Room Height: 9 ft
    • Desired ACH: 10 (a moderate rate for a frequently used space)
  • Calculations:
    • Room Volume = 12 ft × 10 ft × 9 ft = 1080 cu ft
    • Air Exchanges per Minute = 10 ACH / 60 = 0.167 per minute (approx)
    • Required CFM = 1080 cu ft × 0.167 per minute = 180.36 CFM
  • Result: For this home office, a ventilation system or fan capable of delivering approximately 180 CFM would be suitable. This ensures a comfortable and productive environment by maintaining fresh air circulation.

How to Use This CFM Calculator

Our CFM Calculator is designed for simplicity and accuracy. Follow these steps to determine your ventilation needs:

  1. Measure Your Space: Accurately measure the length, width, and height of the room or area you need to ventilate. Ensure you measure wall-to-wall for length and width, and floor-to-ceiling for height.
  2. Determine Desired Air Changes per Hour (ACH): Consider the purpose of the room. Use the table provided or consult relevant building codes and HVAC guidelines. Higher ACH is needed for spaces where pollutants, moisture, or odors are generated quickly (like kitchens or bathrooms), while moderate ACH is sufficient for general living areas or offices.
  3. Enter Values: Input your measurements (in feet) and the desired ACH into the calculator fields.
  4. Calculate: Click the "Calculate CFM" button. The calculator will instantly display the required CFM.

How to Read Results:

  • Required CFM: This is the primary result, indicating the airflow capacity your fan or ventilation system needs to meet your specified ACH.
  • Room Volume (cu ft): This shows the total cubic space of your room, a key component in the calculation.
  • Air Exchanges / Min: This indicates how many times per minute the entire air volume of your room is processed by the ventilation system.

Decision-Making Guidance:

Once you have your CFM requirement, use it to select appropriate ventilation equipment. Always choose a fan or system with a CFM rating that meets or slightly exceeds your calculated need. Consider factors like noise level (measured in sones), energy efficiency, and ductwork compatibility. For complex systems or critical applications, consulting with an HVAC professional is highly recommended.

Key Factors That Affect CFM Results

While the basic CFM calculation provides a solid starting point, several other factors can influence the actual airflow requirements and system performance:

  • Room Size and Volume: This is the most direct factor. Larger rooms naturally require higher CFM to achieve the same ACH.
  • Purpose and Usage of the Space: Rooms with higher levels of activity, heat generation, or pollutant/moisture production (e.g., kitchens, gyms, workshops) require significantly higher ACH and thus higher CFM.
  • Occupancy Load: Higher occupancy means more CO2 and moisture generated, necessitating increased ventilation rates (higher ACH).
  • External Air Quality: In areas with poor outdoor air quality, ventilation systems might need to balance airflow with the use of high-efficiency filters to avoid drawing in pollutants. Sometimes, this means adjusting the ACH downwards if filtration is extremely effective.
  • Building Envelope Tightness: Tightly sealed, modern homes may rely more on mechanical ventilation to ensure fresh air, while older, leakier homes might have sufficient infiltration. However, controlled mechanical ventilation is always preferred for consistency.
  • Ductwork Design and Static Pressure: The length, diameter, bends, and material of ductwork, as well as the resistance from filters and vents, create static pressure. This pressure drop reduces the actual airflow a fan can deliver. Fans must be selected considering their performance curve against the system's static pressure. A fan's rated CFM is often measured under ideal, unobstructed conditions.
  • Heat Load: In spaces with significant heat sources (e.g., server rooms, commercial kitchens), ventilation must also account for heat removal, potentially requiring higher airflow.
  • Specific Pollutant Control: For specialized applications like removing hazardous fumes (e.g., welding, chemical labs), much higher CFM rates and specific exhaust system designs are mandatory, often governed by strict safety regulations.

Frequently Asked Questions (FAQ)

What is a good ACH for a living room?
For a typical residential living room, an ACH of 4-8 is generally recommended. This ensures adequate air circulation for comfort and removes common indoor air pollutants without excessive energy use.
Can I use the same CFM for different rooms?
No, it's not advisable. Different rooms have different purposes, sizes, and potential pollutant sources, requiring tailored ACH rates and therefore different CFM calculations. Always calculate CFM for each specific space.
What if my calculated CFM is very high?
A very high CFM might indicate an unusually large room, a need for very frequent air changes (like in a laboratory), or potentially an issue with the ACH target. Review your measurements and the appropriateness of your chosen ACH. If the requirement remains high, ensure your chosen fan or system can handle the load and consider energy efficiency.
How does fan noise (sones) relate to CFM?
Generally, fans with higher CFM ratings tend to be noisier, although modern designs have improved this. Noise is measured in sones. When selecting a fan, balance the required CFM with an acceptable sone rating for the specific room.
Does CFM affect heating and cooling?
Yes, indirectly. While CFM primarily measures air movement for ventilation, the same fans and ductwork are often used for your HVAC system. Adequate airflow (measured in CFM) is critical for efficient heating and cooling distribution throughout your home. Insufficient CFM can lead to uneven temperatures.
What is the difference between CFM and static pressure?
CFM is the volume of air moved, while static pressure is the resistance the fan must overcome (e.g., from ducts, filters). A fan's CFM rating is often specified at zero static pressure. As static pressure increases, the actual delivered CFM decreases. It's essential to choose a fan rated for the static pressure of your system.
Are there building codes that dictate CFM requirements?
Yes, building codes (like ASHRAE standards or local building codes) often specify minimum ventilation rates (ACH or CFM per square foot) for different types of spaces to ensure occupant health and safety. It's crucial to be aware of and comply with these codes.
Can I use square footage instead of volume for calculations?
While some simpler guidelines use CFM per square foot (especially for exhaust fans in small spaces like bathrooms), the volume-based calculation (using cubic feet and ACH) is more accurate for general ventilation as it accounts for the room's height. The "Estimated CFM per 100 sq ft" in our table provides a quick reference based on typical room heights and ACH targets.

© Your Company Name. All rights reserved.

var currentYear = new Date().getFullYear(); document.getElementById("currentYear").textContent = currentYear; function validateInput(id, min, max) { var element = document.getElementById(id); var errorElement = document.getElementById(id + "Error"); var value = parseFloat(element.value); errorElement.style.display = 'none'; // Hide previous error element.style.borderColor = '#ccc'; // Reset border color if (isNaN(value)) { errorElement.textContent = "Please enter a valid number."; errorElement.style.display = 'block'; element.style.borderColor = '#dc3545'; return false; } if (value <= 0) { errorElement.textContent = "Value must be positive."; errorElement.style.display = 'block'; element.style.borderColor = '#dc3545'; return false; } if (id === "airChangesPerHour" && (value 100)) { errorElement.textContent = "ACH should typically be between 1 and 100."; errorElement.style.display = 'block'; element.style.borderColor = '#dc3545'; return false; } // Add more specific range checks if needed for other inputs return true; } function calculateCfm() { var lengthValid = validateInput("roomLength"); var widthValid = validateInput("roomWidth"); var heightValid = validateInput("roomHeight"); var achValid = validateInput("airChangesPerHour"); if (!lengthValid || !widthValid || !heightValid || !achValid) { return; // Stop calculation if any input is invalid } var roomLength = parseFloat(document.getElementById("roomLength").value); var roomWidth = parseFloat(document.getElementById("roomWidth").value); var roomHeight = parseFloat(document.getElementById("roomHeight").value); var airChangesPerHour = parseFloat(document.getElementById("airChangesPerHour").value); var roomVolume = roomLength * roomWidth * roomHeight; var airExchangesPerMinute = airChangesPerHour / 60; var requiredCfm = roomVolume * airExchangesPerMinute; document.getElementById("calculatedVolume").textContent = roomVolume.toFixed(0); document.getElementById("airExchangesPerMinute").textContent = airExchangesPerMinute.toFixed(2); document.getElementById("requiredCfm").textContent = requiredCfm.toFixed(0); document.getElementById("mainResult").textContent = requiredCfm.toFixed(0) + " CFM"; updateChart(roomVolume, requiredCfm); } function resetCalculator() { document.getElementById("roomLength").value = "15"; document.getElementById("roomWidth").value = "10"; document.getElementById("roomHeight").value = "8"; document.getElementById("airChangesPerHour").value = "10"; // Clear error messages document.getElementById("roomLengthError").textContent = ""; document.getElementById("roomWidthError").textContent = ""; document.getElementById("roomHeightError").textContent = ""; document.getElementById("airChangesPerHourError").textContent = ""; document.getElementById("roomLengthError").style.display = 'none'; document.getElementById("roomWidthError").style.display = 'none'; document.getElementById("roomHeightError").style.display = 'none'; document.getElementById("airChangesPerHourError").style.display = 'none'; // Reset input borders document.getElementById("roomLength").style.borderColor = '#ccc'; document.getElementById("roomWidth").style.borderColor = '#ccc'; document.getElementById("roomHeight").style.borderColor = '#ccc'; document.getElementById("airChangesPerHour").style.borderColor = '#ccc'; // Reset results document.getElementById("calculatedVolume").textContent = "–"; document.getElementById("airExchangesPerMinute").textContent = "–"; document.getElementById("requiredCfm").textContent = "–"; document.getElementById("mainResult").textContent = "– CFM"; updateChart(1200, 100); // Reset chart to default view } function copyResults() { var mainResult = document.getElementById("mainResult").textContent; var calculatedVolume = document.getElementById("calculatedVolume").textContent; var airExchangesPerMinute = document.getElementById("airExchangesPerMinute").textContent; var requiredCfm = document.getElementById("requiredCfm").textContent; var assumptions = "Assumptions:\n"; assumptions += "- Room Volume: " + calculatedVolume + " cu ft\n"; assumptions += "- Air Exchanges/Min: " + airExchangesPerMinute + "\n"; assumptions += "- Formula: CFM = (Volume * ACH) / 60"; var textToCopy = "CFM Calculation Results:\n"; textToCopy += "————————-\n"; textToCopy += "Required CFM: " + mainResult + "\n"; textToCopy += "\n" + assumptions; // Use navigator.clipboard for modern browsers if (navigator.clipboard && navigator.clipboard.writeText) { navigator.clipboard.writeText(textToCopy).then(function() { alert('Results copied to clipboard!'); }).catch(function(err) { console.error('Failed to copy text: ', err); fallbackCopyTextToClipboard(textToCopy); }); } else { fallbackCopyTextToClipboard(textToCopy); } } function fallbackCopyTextToClipboard(text) { var textArea = document.createElement("textarea"); textArea.value = text; textArea.style.position = "fixed"; // Avoid scrolling to bottom textArea.style.top = 0; textArea.style.left = 0; textArea.style.width = '2em'; textArea.style.height = '2em'; textArea.style.padding = '0'; textArea.style.border = 'none'; textArea.style.outline = 'none'; textArea.style.boxShadow = 'none'; textArea.style.background = 'transparent'; document.body.appendChild(textArea); textArea.focus(); textArea.select(); try { var successful = document.execCommand('copy'); var msg = successful ? 'Copied!' : 'Copy failed!'; alert(msg); } catch (err) { console.error('Fallback: Oops, unable to copy', err); alert('Copy failed. Please copy manually.'); } document.body.removeChild(textArea); } // Chart Logic var ctx; var myChart; function initializeChart() { ctx = document.getElementById("cfmChart").getContext("2d"); myChart = new Chart(ctx, { type: 'bar', // Changed to bar for better comparison data: { labels: ['Low ACH (4)', 'Medium ACH (10)', 'High ACH (20)'], datasets: [{ label: 'Required CFM', data: [], // To be populated by updateChart backgroundColor: 'rgba(0, 74, 153, 0.7)', // Primary color borderColor: 'rgba(0, 74, 153, 1)', borderWidth: 1 }, { label: 'Room Volume (1000 cu ft increments)', data: [], // To be populated by updateChart backgroundColor: 'rgba(40, 167, 69, 0.5)', // Success color, slightly transparent borderColor: 'rgba(40, 167, 69, 1)', borderWidth: 1 }] }, options: { responsive: true, maintainAspectRatio: false, scales: { y: { beginAtZero: true, title: { display: true, text: 'CFM / Volume' } }, x: { title: { display: true, text: 'Ventilation Scenario' } } }, plugins: { tooltip: { callbacks: { label: function(context) { var label = context.dataset.label || "; if (label) { label += ': '; } if (context.parsed.y !== null) { label += context.parsed.y + (context.dataset.label.includes('CFM') ? ' CFM' : ' cu ft'); } return label; } } } } } }); // Initial chart render with default values updateChart(1200, 100); // Default values corresponding to 10 ACH for a 15x10x8 room } function updateChart(currentVolume, currentCfm) { if (!myChart) { // Chart not initialized yet, wait for DOM ready or call initializeChart explicitly return; } var currentAch = parseFloat(document.getElementById("airChangesPerHour").value); // Calculate representative volumes and CFM for different ACH scenarios // Assuming a baseline room volume for demonstration var baselineVolume1 = 800; // e.g., 10x10x8 var baselineVolume2 = 1200; // e.g., 15x10x8 var baselineVolume3 = 2000; // e.g., 20x10x10 var ach1 = 4; var ach2 = 10; var ach3 = 20; var cfm1 = (baselineVolume1 * ach1) / 60; var cfm2 = (baselineVolume2 * ach2) / 60; var cfm3 = (baselineVolume3 * ach3) / 60; // Also plot the current user input scenario var labels = ['Scenario 1 (ACH ' + ach1 + ')', 'Scenario 2 (ACH ' + ach2 + ')', 'Scenario 3 (ACH ' + ach3 + ')']; var cfmData = [cfm1.toFixed(0), cfm2.toFixed(0), cfm3.toFixed(0)]; var volumeData = [baselineVolume1, baselineVolume2, baselineVolume3]; // Add current input as another data point or adjust scale labels.push('Your Input (' + currentAch + ' ACH)'); cfmData.push(currentCfm.toFixed(0)); volumeData.push(currentVolume); myChart.data.labels = labels; myChart.data.datasets[0].data = cfmData; myChart.data.datasets[1].data = volumeData; // Showing volume for context // Adjust y-axis to accommodate all data points var allValues = cfmData.concat(volumeData.map(Number)); // Combine all numbers var maxValue = Math.max(…allValues); var yAxisMax = maxValue * 1.1; // Add 10% buffer // Find max volume and max CFM separately for potentially different scales or labels var maxVol = Math.max(…volumeData); var maxCfm = Math.max(…cfmData.map(Number)); myChart.options.scales.y.max = Math.max(maxVol, maxCfm) * 1.15; // Adjust scale dynamically myChart.update(); } // Add event listeners for real-time validation on input change document.getElementById("roomLength").addEventListener("input", function() { validateInput("roomLength"); calculateCfm(); }); document.getElementById("roomWidth").addEventListener("input", function() { validateInput("roomWidth"); calculateCfm(); }); document.getElementById("roomHeight").addEventListener("input", function() { validateInput("roomHeight"); calculateCfm(); }); document.getElementById("airChangesPerHour").addEventListener("input", function() { validateInput("airChangesPerHour"); calculateCfm(); }); // Initialize the chart when the page loads window.onload = function() { initializeChart(); calculateCfm(); // Perform initial calculation on load }; // FAQ Toggle var faqItems = document.querySelectorAll('.faq-item .question'); for (var i = 0; i < faqItems.length; i++) { faqItems[i].addEventListener('click', function() { var parent = this.parentElement; parent.classList.toggle('open'); }); }