Refrigerant Mass Flow Rate Calculator
Calculation Results
Understanding Refrigerant Mass Flow Rate
The refrigerant mass flow rate represents the amount of refrigerant by mass that circulates through a refrigeration or air conditioning system per unit of time. It is a critical parameter in the design and analysis of HVAC systems, determining the sizing of compressors, expansion valves, and piping.
The Mass Flow Formula
The fundamental thermodynamic equation linking cooling capacity and mass flow rate relies on the concept of the Net Refrigerating Effect (NRE). The NRE is the change in enthalpy (energy content) of the refrigerant as it passes through the evaporator.
Where:
- ˙m = Mass Flow Rate (kg/s or lb/min)
- Q = Total Cooling Capacity or Heat Load (kW or BTU/hr)
- Δh = Net Refrigerating Effect (Enthalpyout – Enthalpyin) across the evaporator
How to Determine the Variables
To use this calculator effectively, you need two primary inputs:
- Cooling Capacity: This is the total heat load the system must remove. It is often measured in Tons of Refrigeration (TR), kilo-Watts (kW), or British Thermal Units per hour (BTU/hr).
- Refrigerating Effect: This requires knowing the thermodynamic properties of the specific refrigerant used (e.g., R-410A, R-134a). You subtract the enthalpy of the refrigerant entering the evaporator from the enthalpy leaving the evaporator. These values are typically found using a Pressure-Enthalpy (P-h) chart.
Example Calculation
Consider a commercial chiller utilizing R-134a with a required cooling capacity of 10 Tons.
- Capacity (Q): 10 Tons. Converting to kW: 10 × 3.517 = 35.17 kW.
- Enthalpy Data:
- Enthalpy at Evaporator Outlet (hg): 400 kJ/kg
- Enthalpy at Evaporator Inlet (hf): 250 kJ/kg
- Net Effect (Δh): 400 – 250 = 150 kJ/kg
Calculation:
˙m = 35.17 kW / 150 kJ/kg = 0.2345 kg/s
This value determines the volume that the compressor must displace to maintain the cooling cycle.
Why Mass Flow Rate Matters
If the mass flow rate is too low, the system cannot absorb enough heat to meet the cooling load, leading to high indoor temperatures. Conversely, if the flow rate is excessively high compared to the components' capacity, it can lead to liquid flood-back into the compressor (damaging the equipment) or inefficient operation due to high pressure drops in the piping.