Inrush Current Calculation

Inrush Current Calculation: Understand and Calculate Peak Motor Startup Current :root { –primary-color: #004a99; –success-color: #28a745; –background-color: #f8f9fa; –text-color: #333; –border-color: #ddd; –card-background: #fff; –shadow: 0 2px 5px rgba(0,0,0,0.1); } body { font-family: 'Segoe UI', Tahoma, Geneva, Verdana, sans-serif; background-color: var(–background-color); color: var(–text-color); line-height: 1.6; margin: 0; padding: 0; display: flex; flex-direction: column; align-items: center; padding-top: 20px; padding-bottom: 40px; } .container { width: 100%; max-width: 960px; margin: 0 auto; padding: 0 15px; box-sizing: border-box; } header { background-color: var(–primary-color); color: white; padding: 20px 0; text-align: center; width: 100%; margin-bottom: 30px; } header h1 { margin: 0; font-size: 2.5em; font-weight: 700; } main { width: 100%; display: flex; flex-direction: column; align-items: center; } section { background-color: var(–card-background); border-radius: 8px; box-shadow: var(–shadow); padding: 30px; margin-bottom: 30px; width: 100%; box-sizing: border-box; } h2, h3 { color: var(–primary-color); margin-top: 0; } .calculator-section { display: flex; flex-direction: column; align-items: center; } .loan-calc-container { background-color: var(–card-background); border-radius: 8px; box-shadow: var(–shadow); padding: 30px; margin-bottom: 30px; width: 100%; box-sizing: border-box; display: flex; flex-direction: column; align-items: center; } .loan-calc-container h2 { text-align: center; margin-bottom: 25px; } .input-group { margin-bottom: 20px; width: 100%; max-width: 400px; display: flex; flex-direction: column; } .input-group label { display: block; margin-bottom: 8px; font-weight: 600; color: var(–primary-color); } .input-group input[type="number"], .input-group select { width: 100%; padding: 12px; border: 1px solid var(–border-color); border-radius: 5px; box-sizing: border-box; font-size: 1em; } .input-group input[type="number"]:focus, .input-group select:focus { outline: none; border-color: var(–primary-color); box-shadow: 0 0 0 2px rgba(0, 74, 153, 0.2); } .input-group .helper-text { font-size: 0.85em; color: #666; margin-top: 5px; } .input-group .error-message { color: red; font-size: 0.8em; margin-top: 5px; height: 1.2em; /* Reserve space for error message */ } .button-group { display: flex; justify-content: center; gap: 15px; margin-top: 25px; flex-wrap: wrap; } button { padding: 12px 25px; border: none; border-radius: 5px; cursor: pointer; font-size: 1em; font-weight: 600; transition: background-color 0.3s ease; } .btn-calculate { background-color: var(–primary-color); color: white; } .btn-calculate:hover { background-color: #003366; } .btn-reset { background-color: #6c757d; color: white; } .btn-reset:hover { background-color: #5a6268; } .btn-copy { background-color: var(–success-color); color: white; } .btn-copy:hover { background-color: #218838; } #results-container { margin-top: 30px; width: 100%; max-width: 400px; text-align: center; background-color: var(–card-background); border-radius: 8px; box-shadow: var(–shadow); padding: 25px; box-sizing: border-box; } #results-container h3 { margin-bottom: 20px; color: var(–primary-color); } .primary-result { font-size: 2.2em; font-weight: 700; color: var(–success-color); margin-bottom: 15px; padding: 10px; background-color: #e9f7ef; border-radius: 5px; display: inline-block; } .intermediate-results div, .formula-explanation { margin-bottom: 10px; font-size: 0.95em; } .intermediate-results strong { color: var(–primary-color); min-width: 200px; display: inline-block; text-align: right; margin-right: 10px; } .formula-explanation { font-style: italic; color: #555; margin-top: 15px; border-top: 1px dashed var(–border-color); padding-top: 15px; } table { width: 100%; border-collapse: collapse; margin-top: 20px; box-shadow: var(–shadow); border-radius: 5px; overflow: hidden; } th, td { padding: 12px 15px; text-align: left; border-bottom: 1px solid var(–border-color); } thead th { background-color: var(–primary-color); color: white; font-weight: 700; } tbody tr:nth-child(even) { background-color: #f2f2f2; } tbody tr:hover { background-color: #e9ecef; } caption { caption-side: bottom; font-size: 0.85em; color: #666; margin-top: 10px; text-align: center; } canvas { display: block; margin: 20px auto; max-width: 100%; border: 1px solid var(–border-color); border-radius: 5px; } .chart-container { text-align: center; margin-top: 20px; } .chart-container h3 { margin-bottom: 15px; } .article-content { width: 100%; background-color: var(–card-background); border-radius: 8px; box-shadow: var(–shadow); padding: 30px; box-sizing: border-box; margin-top: 30px; } .article-content h2 { border-bottom: 2px solid var(–primary-color); padding-bottom: 8px; margin-bottom: 20px; } .article-content h3 { margin-top: 25px; margin-bottom: 15px; color: #0056b3; } .article-content p { margin-bottom: 15px; } .article-content ul, .article-content ol { margin-left: 20px; margin-bottom: 15px; } .article-content li { margin-bottom: 8px; } .faq-list .faq-item { margin-bottom: 15px; border-left: 3px solid var(–primary-color); padding-left: 15px; } .faq-list .faq-item strong { display: block; color: var(–primary-color); margin-bottom: 5px; } .internal-links { margin-top: 30px; background-color: var(–card-background); border-radius: 8px; box-shadow: var(–shadow); padding: 30px; width: 100%; box-sizing: border-box; } .internal-links h3 { text-align: center; margin-bottom: 20px; } .internal-links ul { list-style: none; padding: 0; display: flex; flex-direction: column; gap: 15px; } .internal-links li { border-bottom: 1px solid var(–border-color); padding-bottom: 10px; } .internal-links li:last-child { border-bottom: none; } .internal-links a { color: var(–primary-color); text-decoration: none; font-weight: 600; } .internal-links a:hover { text-decoration: underline; } .internal-links span { display: block; font-size: 0.9em; color: #555; margin-top: 5px; } footer { text-align: center; margin-top: 40px; font-size: 0.8em; color: #777; } @media (min-width: 768px) { .loan-calc-container { flex-direction: column; } .button-group { flex-direction: row; } }

Inrush Current Calculator

Calculate Motor Inrush Current

Enter the motor's rated horsepower.
Typical power factor during startup (e.g., 0.2 to 0.8).
Motor efficiency at rated load (e.g., 80-95%).
The operating voltage of the electrical system.
Factor by which inrush current exceeds Full Load Amps (FLA). Typically 5-10x.

Calculation Results

— A
Full Load Amps (FLA): — A
Peak Inrush Current: — A
Starting Torque (approx): — %
Formula: Inrush Current (A) = (Motor Power (HP) * 746) / (Voltage (V) * Power Factor * Efficiency / 100) * Inrush Multiplier
Starting Torque is often estimated as a percentage of rated torque, influenced by motor design and inrush.

Inrush vs. Full Load Current Over Time

Comparison of motor current during startup and steady operation.

Calculation Details Table

Parameter Value Unit
Motor Power HP
Power Factor
Efficiency %
Line Voltage V
Inrush Multiplier xFLA
Full Load Amps (FLA) A
Peak Inrush Current A
Approx. Starting Torque %
Detailed breakdown of input parameters and calculated values.

What is Inrush Current Calculation?

Inrush current calculation is the process of determining the exceptionally high, transient current that an electrical device, most notably an electric motor, draws when it is first energized or switched on. This phenomenon, also known as startup current or motor-starting current, is a critical consideration in electrical system design and motor protection. Understanding and accurately calculating inrush current is vital for ensuring the reliability, safety, and efficiency of electrical installations. It helps engineers and technicians select appropriate circuit protection devices (like fuses and circuit breakers), size conductors correctly, and prevent nuisance tripping or equipment damage.

Who should use it: This calculation is essential for electrical engineers, motor control specialists, maintenance technicians, industrial electricians, and anyone involved in designing, installing, or maintaining electrical systems that power motors. It's also useful for manufacturers of electrical equipment and control panels.

Common misconceptions: A frequent misconception is that inrush current is simply a slightly higher version of the motor's normal operating current. In reality, inrush current can be many times (typically 5 to 10 times, but sometimes much higher) the motor's Full Load Amps (FLA). Another misconception is that inrush current is a constant value; it's a transient event that decays rapidly as the motor accelerates. Some also believe that standard circuit breakers are always sufficient without considering the specific inrush characteristics of the motor.

Inrush Current Formula and Mathematical Explanation

The calculation of inrush current involves several steps, starting with determining the motor's Full Load Amps (FLA) and then applying a multiplier to estimate the peak startup current.

Step 1: Calculate Full Load Amps (FLA) The FLA is the current a motor draws when operating at its rated horsepower under full load conditions. It's calculated using the motor's power rating, voltage, power factor, and efficiency.

The formula for FLA is derived from the basic electrical power equation: Power (Watts) = Voltage (Volts) × Current (Amps) × Power Factor

Since 1 Horsepower (HP) is approximately 746 Watts, we can adapt this for motors: Mechanical Output Power (Watts) = Voltage (V) × Current (A) × Power Factor (PF) × Efficiency (η)

Rearranging to solve for Current (FLA): FLA (Amps) = (Motor Power (HP) × 746) / (Voltage (V) × Power Factor (PF) × (Efficiency (%) / 100))

Step 2: Calculate Peak Inrush Current Electric motors exhibit a high inrush current due to the inductive nature of their windings and the initial state of the rotor. This inrush current is typically expressed as a multiple of the FLA.

Peak Inrush Current (Amps) = FLA (Amps) × Inrush Multiplier (xFLA)

The "Inrush Multiplier" is a factor provided by the motor manufacturer or estimated based on motor type and application, commonly ranging from 5 to 10 times the FLA for standard induction motors.

Starting Torque Estimation: While not directly calculated from the primary formula, starting torque is a crucial related parameter. It's often expressed as a percentage of the motor's rated torque. High inrush current is generally associated with high starting torque, which is necessary to overcome inertia and bring the load up to speed. Typical starting torque can range from 150% to 300% of rated torque for standard motors, but this varies significantly with motor design (e.g., NEMA design classes A, B, C, D).

Variables Table:

Variable Meaning Unit Typical Range
Motor Power Rated mechanical output power of the motor. HP (Horsepower) 0.5 – 500+
Voltage Operating line voltage of the electrical system. V (Volts) 115, 208, 230, 460, 575, etc.
Power Factor (PF) Ratio of real power to apparent power; indicates phase difference between voltage and current. Lower during startup. – (dimensionless) 0.2 – 0.8 (startup)
Efficiency (η) Ratio of output mechanical power to input electrical power. % 80 – 95%
Inrush Multiplier Factor representing how many times the FLA the motor draws during startup. xFLA 5 – 10 (standard induction motors)
FLA Full Load Amps: Current drawn at rated load. A (Amperes) Varies widely with motor size
Peak Inrush Current Maximum instantaneous current drawn during startup. A (Amperes) Varies widely
Starting Torque Torque produced by the motor at zero speed. % of Rated Torque 150% – 300% (typical)

Practical Examples (Real-World Use Cases)

Example 1: Standard Industrial Motor

An engineer is specifying a 25 HP motor for a conveyor system. The motor operates at 460V, has a rated Power Factor of 0.85, and an Efficiency of 92%. The motor manufacturer indicates a typical Inrush Multiplier of 6x FLA.

Inputs:

  • Motor Power: 25 HP
  • Voltage: 460 V
  • Power Factor: 0.85
  • Efficiency: 92%
  • Inrush Multiplier: 6

Calculation:

  1. FLA = (25 HP * 746) / (460 V * 0.85 * (92 / 100)) = 18650 / (460 * 0.85 * 0.92) ≈ 18650 / 359.48 ≈ 51.88 A
  2. Peak Inrush Current = 51.88 A * 6 ≈ 311.28 A

Interpretation: This 25 HP motor will draw approximately 51.9 Amps under normal full load. However, at startup, it will momentarily draw about 311.3 Amps. The electrical system, including the circuit breaker and wiring, must be sized to handle this high inrush current without tripping or overheating. A breaker rated for continuous operation at 51.9A might need a higher instantaneous trip setting or a time-delay characteristic to accommodate the startup surge.

Example 2: Small HVAC Fan Motor

A technician is troubleshooting a small 3 HP fan motor in an HVAC unit. The system voltage is 230V. The motor nameplate is partially worn, but they estimate the Power Factor at startup to be around 0.3 and the Efficiency at 88%. They know from experience that similar motors have an Inrush Multiplier of 7x FLA.

Inputs:

  • Motor Power: 3 HP
  • Voltage: 230 V
  • Power Factor: 0.3
  • Efficiency: 88%
  • Inrush Multiplier: 7

Calculation:

  1. FLA = (3 HP * 746) / (230 V * 0.3 * (88 / 100)) = 2238 / (230 * 0.3 * 0.88) ≈ 2238 / 60.72 ≈ 36.86 A
  2. Peak Inrush Current = 36.86 A * 7 ≈ 258.02 A

Interpretation: This 3 HP fan motor has a Full Load Amps of approximately 36.9 Amps. The startup inrush current can reach about 258 Amps. This high inrush, especially with a low startup power factor, could be causing the circuit breaker to trip intermittently. The technician might need to consider a time-delay fuse or breaker, or investigate if the motor is failing and drawing excessive current even during normal operation. The low estimated power factor during startup is typical for many motors.

How to Use This Inrush Current Calculator

Our Inrush Current Calculator is designed for simplicity and accuracy. Follow these steps to get your results:

  1. Enter Motor Power: Input the motor's rated power in Horsepower (HP).
  2. Input Power Factor: Enter the motor's power factor during startup. This is often lower than the running PF, typically between 0.2 and 0.8. If unsure, use a conservative estimate or consult motor data.
  3. Specify Efficiency: Enter the motor's efficiency percentage at rated load. This is usually found on the motor nameplate.
  4. Provide Line Voltage: Enter the operating voltage of the electrical system in Volts (V).
  5. Set Inrush Multiplier: Input the factor by which the inrush current exceeds the Full Load Amps (FLA). This is often provided by the motor manufacturer (e.g., 6x FLA).
  6. Click Calculate: Press the "Calculate" button.

How to read results:

  • Primary Result (Peak Inrush Current): This is the main output, displayed prominently in Amperes (A). It represents the maximum current the motor will draw momentarily upon startup.
  • Full Load Amps (FLA): This value shows the motor's normal operating current under full load.
  • Peak Inrush Current: This reiterates the main result for clarity.
  • Approx. Starting Torque: This provides an estimated percentage of the motor's rated torque at startup, indicating its ability to start the load.
  • Table and Chart: The table provides a detailed breakdown of all inputs and calculated values. The chart visually compares the FLA to the peak inrush current.

Decision-making guidance: Use the calculated Peak Inrush Current to:

  • Size Circuit Protection: Ensure fuses or circuit breakers are rated appropriately to withstand the inrush without tripping nuisance, while still providing overcurrent protection. Time-delay breakers are often recommended for motor circuits.
  • Select Conductors: Verify that the wiring gauge is sufficient to handle the peak current without excessive voltage drop or overheating.
  • Assess Power System Capacity: Ensure the overall electrical system can handle the momentary load increase without affecting other connected equipment.
  • Choose Motor Starters: Select appropriate motor starters (e.g., direct-on-line, star-delta) based on the motor size and inrush characteristics.

Key Factors That Affect Inrush Current Results

Several factors influence the magnitude and duration of inrush current in electric motors:

  • Motor Design and Type: Different motor designs (e.g., NEMA Design B, C, D) have inherently different starting characteristics. High-torque motors often have higher inrush currents. Squirrel cage induction motors are most common, but synchronous or DC motors have different startup behaviors.
  • Rotor Resistance: Higher rotor resistance generally leads to higher starting torque and potentially higher inrush current, especially in wound rotor motors.
  • Voltage Sag: A significant drop in supply voltage during startup (voltage sag) can drastically increase the inrush current as the motor attempts to draw more current to compensate. This is why system capacity is crucial.
  • Load Inertia: The inertia of the driven load affects how quickly the motor accelerates. A heavier or more difficult load might require a longer acceleration time, potentially influencing the duration of the inrush current phase, though the peak value is primarily determined by motor characteristics.
  • Temperature: Motor winding resistance increases with temperature. A cold motor (at startup) has lower resistance, which can slightly affect the initial current draw compared to a warm motor. However, the dominant factor is the magnetic field build-up.
  • Starting Method: The method used to start the motor significantly impacts the inrush current. Direct-on-line (DOL) starting results in the highest inrush. Reduced voltage starting methods like star-delta, autotransformer, or soft starters are employed specifically to limit this high inrush current.
  • Power Factor and Efficiency: As seen in the formula, lower power factor and efficiency during startup directly increase the calculated FLA and, consequently, the inrush current. These values are often estimated or obtained from motor data sheets.

Frequently Asked Questions (FAQ)

Q1: What is the difference between inrush current and locked rotor current (LRA)?

Inrush current is the general term for the high transient current drawn when a motor starts. Locked Rotor Amps (LRA) specifically refers to the current drawn when the motor's rotor is prevented from rotating (i.e., stalled at 0 RPM). LRA is typically the maximum current the motor will ever draw and is often used as a reference point for sizing protection devices. Inrush current is usually slightly less than LRA but still significantly higher than FLA.

Q2: Why is inrush current so much higher than normal running current?

When a motor is stationary, its rotor is not moving, and there is no back electromotive force (back EMF) generated. Back EMF opposes the applied voltage, reducing the net voltage across the windings and thus limiting the current during normal operation. At startup, the absence of back EMF allows the full supply voltage (minus impedance) to drive a very large current through the windings. As the motor accelerates, back EMF builds up, and the current decreases towards the FLA.

Q3: Can inrush current damage my electrical system?

Yes, if not properly accounted for. Excessive inrush current can cause nuisance tripping of circuit breakers or blowing of fuses. It can also lead to voltage sags on the power system, affecting other sensitive equipment. Repeatedly subjecting components to high inrush currents without adequate protection can shorten their lifespan.

Q4: How do I choose the right circuit breaker for a motor?

Motor circuit breakers need to handle the high inrush current without tripping unnecessarily, but still protect against sustained overloads and short circuits. This often involves using inverse-time (thermal-magnetic) breakers with specific trip curves or time-delay fuses designed for motor loads. The breaker's trip rating and characteristics should be selected based on the motor's FLA, LRA, and the National Electrical Code (NEC) or local regulations.

Q5: What is the typical inrush multiplier for different motor types?

For standard NEMA Design B squirrel cage induction motors, the inrush multiplier is typically 5 to 7 times FLA. NEMA Design C motors might have slightly lower inrush but higher starting torque. NEMA Design D motors have very high starting torque and can have inrush multipliers of 8 to 10 times FLA or more. Specific values should always be confirmed with the motor manufacturer.

Q6: Does the power factor change during startup?

Yes, significantly. The power factor of an induction motor is typically high (0.8 to 0.95) when running at full load. However, during startup, due to the low rotor speed and high current, the power factor is much lower, often in the range of 0.2 to 0.5, sometimes even lower for very large motors or specific designs. This low startup power factor contributes to the high apparent power (kVA) demand.

Q7: Can I use the same calculation for AC and DC motors?

No. This calculator is specifically designed for AC induction motors. DC motors have different starting characteristics. While they also draw high starting currents due to low initial resistance and lack of back EMF, the calculation methods and typical values differ. DC motor starting often involves external resistors to limit current.

Q8: What is the role of a soft starter in managing inrush current?

A soft starter is an electronic device that gradually increases the voltage supplied to the motor during startup. By controlling the voltage ramp, it effectively limits the inrush current and reduces mechanical shock. This controlled startup protects the motor, the driven load, and the electrical system from the stresses associated with high transient currents.

Related Tools and Internal Resources

© 2023 Your Company Name. All rights reserved.

var motorPowerInput = document.getElementById('motorPower'); var powerFactorInput = document.getElementById('powerFactor'); var efficiencyInput = document.getElementById('efficiency'); var voltageInput = document.getElementById('voltage'); var inrushMultiplierInput = document.getElementById('inrushMultiplier'); var motorPowerError = document.getElementById('motorPowerError'); var powerFactorError = document.getElementById('powerFactorError'); var efficiencyError = document.getElementById('efficiencyError'); var voltageError = document.getElementById('voltageError'); var inrushMultiplierError = document.getElementById('inrushMultiplierError'); var inrushCurrentResult = document.getElementById('inrushCurrentResult'); var fullLoadAmpsResult = document.getElementById('fullLoadAmpsResult'); var peakInrushAmpsResult = document.getElementById('peakInrushAmpsResult'); var startingTorqueResult = document.getElementById('startingTorqueResult'); var tableMotorPower = document.getElementById('tableMotorPower'); var tablePowerFactor = document.getElementById('tablePowerFactor'); var tableEfficiency = document.getElementById('tableEfficiency'); var tableVoltage = document.getElementById('tableVoltage'); var tableInrushMultiplier = document.getElementById('tableInrushMultiplier'); var tableFLA = document.getElementById('tableFLA'); var tablePeakInrush = document.getElementById('tablePeakInrush'); var tableStartingTorque = document.getElementById('tableStartingTorque'); var ctx = document.getElementById('inrushChart').getContext('2d'); var inrushChart = null; function validateInput(value, min, max, errorElement, inputElement, fieldName) { var errorMsg = ""; if (isNaN(value) || value === "") { errorMsg = fieldName + " is required."; inputElement.style.borderColor = 'red'; } else if (value max) { errorMsg = fieldName + " must be between " + min + " and " + max + "."; inputElement.style.borderColor = 'red'; } else { inputElement.style.borderColor = '#ddd'; } if (errorElement) { errorElement.textContent = errorMsg; } return errorMsg === ""; } function calculateInrushCurrent() { var motorPower = parseFloat(motorPowerInput.value); var powerFactor = parseFloat(powerFactorInput.value); var efficiency = parseFloat(efficiencyInput.value); var voltage = parseFloat(voltageInput.value); var inrushMultiplier = parseFloat(inrushMultiplierInput.value); var isValid = true; isValid &= validateInput(motorPower, 0.1, 1000, motorPowerError, motorPowerInput, "Motor Power"); isValid &= validateInput(powerFactor, 0.1, 1.0, powerFactorError, powerFactorInput, "Power Factor"); isValid &= validateInput(efficiency, 1, 100, efficiencyError, efficiencyInput, "Efficiency"); isValid &= validateInput(voltage, 1, 1000, voltageError, voltageInput, "Voltage"); isValid &= validateInput(inrushMultiplier, 1, 20, inrushMultiplierError, inrushMultiplierInput, "Inrush Multiplier"); if (!isValid) { inrushCurrentResult.textContent = "– A"; fullLoadAmpsResult.innerHTML = "Full Load Amps (FLA): — A"; peakInrushAmpsResult.innerHTML = "Peak Inrush Current: — A"; startingTorqueResult.innerHTML = "Starting Torque (approx): — %"; updateTable('–', '–', '–', '–', '–', '–', '–', '–'); updateChart([0, 0], [0, 0]); return; } var efficiencyDecimal = efficiency / 100; var fullLoadAmps = (motorPower * 746) / (voltage * powerFactor * efficiencyDecimal); var peakInrushCurrent = fullLoadAmps * inrushMultiplier; // Approximate starting torque calculation (highly variable, this is a simplified representation) // Torque is roughly proportional to the square of the voltage and inversely proportional to impedance. // For simplicity, we'll relate it loosely to inrush multiplier and a base torque. // A common assumption is starting torque is 150-250% of rated torque for standard motors. // Let's use a heuristic: higher inrush multiplier might imply higher torque needs. var estimatedStartingTorque = 150 + (inrushMultiplier – 5) * 15; // Example heuristic if (estimatedStartingTorque > 300) estimatedStartingTorque = 300; if (estimatedStartingTorque < 100) estimatedStartingTorque = 100; inrushCurrentResult.textContent = peakInrushCurrent.toFixed(2) + " A"; fullLoadAmpsResult.innerHTML = "Full Load Amps (FLA): " + fullLoadAmps.toFixed(2) + " A"; peakInrushAmpsResult.innerHTML = "Peak Inrush Current: " + peakInrushCurrent.toFixed(2) + " A"; startingTorqueResult.innerHTML = "Starting Torque (approx): " + estimatedStartingTorque.toFixed(0) + " %"; updateTable(motorPower.toFixed(1), powerFactor.toFixed(2), efficiency.toFixed(1), voltage.toFixed(0), inrushMultiplier.toFixed(1), fullLoadAmps.toFixed(2), peakInrushCurrent.toFixed(2), estimatedStartingTorque.toFixed(0)); updateChart(fullLoadAmps, peakInrushCurrent); } function updateTable(mp, pf, eff, v, im, fla, pir, st) { tableMotorPower.textContent = mp; tablePowerFactor.textContent = pf; tableEfficiency.textContent = eff; tableVoltage.textContent = v; tableInrushMultiplier.textContent = im; tableFLA.textContent = fla; tablePeakInrush.textContent = pir; tableStartingTorque.textContent = st; } function updateChart(flaValue, peakInrushValue) { if (inrushChart) { inrushChart.destroy(); } var labels = ['Full Load Amps (FLA)', 'Peak Inrush Current']; var data = [flaValue, peakInrushValue]; // Adjust scale dynamically if needed var maxData = Math.max(…data); var yAxisMax = maxData * 1.2; // Add some padding ctx.canvas.height = 250; // Set a fixed height for the canvas inrushChart = new Chart(ctx, { type: 'bar', data: { labels: labels, datasets: [{ label: 'Current (Amps)', data: data, backgroundColor: [ 'rgba(0, 74, 153, 0.6)', // Primary color for FLA 'rgba(40, 167, 69, 0.6)' // Success color for Peak Inrush ], borderColor: [ 'rgba(0, 74, 153, 1)', 'rgba(40, 167, 69, 1)' ], borderWidth: 1 }] }, options: { responsive: true, maintainAspectRatio: false, scales: { y: { beginAtZero: true, max: yAxisMax, title: { display: true, text: 'Current (Amps)' } } }, plugins: { legend: { display: false // Hide legend as labels are on the bars }, title: { display: true, text: 'Motor Current Comparison' } } } }); } function resetCalculator() { motorPowerInput.value = '10'; powerFactorInput.value = '0.8'; efficiencyInput.value = '90'; voltageInput.value = '230'; inrushMultiplierInput.value = '6'; motorPowerError.textContent = ""; powerFactorError.textContent = ""; efficiencyError.textContent = ""; voltageError.textContent = ""; inrushMultiplierError.textContent = ""; motorPowerInput.style.borderColor = '#ddd'; powerFactorInput.style.borderColor = '#ddd'; efficiencyInput.style.borderColor = '#ddd'; voltageInput.style.borderColor = '#ddd'; inrushMultiplierInput.style.borderColor = '#ddd'; calculateInrushCurrent(); // Recalculate with default values } function copyResults() { var resultsText = "Inrush Current Calculation Results:\n\n"; resultsText += "Motor Power: " + motorPowerInput.value + " HP\n"; resultsText += "Power Factor: " + powerFactorInput.value + "\n"; resultsText += "Efficiency: " + efficiencyInput.value + " %\n"; resultsText += "Voltage: " + voltageInput.value + " V\n"; resultsText += "Inrush Multiplier: " + inrushMultiplierInput.value + " xFLA\n\n"; resultsText += "Full Load Amps (FLA): " + (document.getElementById('fullLoadAmpsResult').textContent.replace('Full Load Amps (FLA): ', ").replace(' A', ")) + "\n"; resultsText += "Peak Inrush Current: " + (document.getElementById('peakInrushAmpsResult').textContent.replace('Peak Inrush Current: ', ").replace(' A', ")) + "\n"; resultsText += "Approx. Starting Torque: " + (document.getElementById('startingTorqueResult').textContent.replace('Starting Torque (approx): ', ").replace(' %', ")) + "\n\n"; resultsText += "Key Assumptions:\n"; resultsText += "- Startup Power Factor used for FLA calculation.\n"; resultsText += "- Inrush Multiplier is an estimate or manufacturer specification.\n"; resultsText += "- Starting Torque is an approximation.\n"; try { navigator.clipboard.writeText(resultsText).then(function() { alert('Results copied to clipboard!'); }).catch(function(err) { console.error('Failed to copy results: ', err); alert('Failed to copy results. Please copy manually.'); }); } catch (e) { console.error('Clipboard API not available: ', e); alert('Clipboard API not available. Please copy results manually.'); } } // Initial calculation on page load document.addEventListener('DOMContentLoaded', function() { calculateInrushCurrent(); // Ensure chart is initialized correctly on load var initialFla = parseFloat(fullLoadAmpsResult.textContent.split(':')[1].replace(' A', ").trim()) || 0; var initialPeak = parseFloat(peakInrushAmpsResult.textContent.split(':')[1].replace(' A', ").trim()) || 0; updateChart(initialFla, initialPeak); }); // Add event listeners for real-time updates motorPowerInput.addEventListener('input', calculateInrushCurrent); powerFactorInput.addEventListener('input', calculateInrushCurrent); efficiencyInput.addEventListener('input', calculateInrushCurrent); voltageInput.addEventListener('input', calculateInrushCurrent); inrushMultiplierInput.addEventListener('input', calculateInrushCurrent);