Calculating Superheat

Superheat Calculator: Calculate and Understand Refrigerant Superheat :root { –primary-color: #004a99; –success-color: #28a745; –background-color: #f8f9fa; –text-color: #333; –border-color: #ddd; –shadow-color: rgba(0, 0, 0, 0.1); –card-background: #fff; } body { font-family: 'Segoe UI', Tahoma, Geneva, Verdana, sans-serif; background-color: var(–background-color); color: var(–text-color); line-height: 1.6; margin: 0; padding: 0; } .container { max-width: 1000px; margin: 20px auto; padding: 20px; background-color: var(–card-background); border-radius: 8px; box-shadow: 0 4px 15px var(–shadow-color); } h1, h2, h3 { color: var(–primary-color); text-align: center; } h1 { margin-bottom: 10px; } h2 { margin-top: 30px; margin-bottom: 15px; border-bottom: 2px solid var(–primary-color); padding-bottom: 5px; } h3 { margin-top: 20px; margin-bottom: 10px; } .calculator-section { background-color: var(–card-background); padding: 25px; border-radius: 8px; box-shadow: 0 2px 10px var(–shadow-color); margin-bottom: 30px; } .loan-calc-container { display: flex; flex-direction: column; gap: 15px; } .input-group { display: flex; flex-direction: column; gap: 5px; } .input-group label { font-weight: bold; color: var(–primary-color); } .input-group input, .input-group select { padding: 10px; border: 1px solid var(–border-color); border-radius: 4px; font-size: 1rem; width: 100%; box-sizing: border-box; } .input-group input:focus, .input-group select:focus { outline: none; border-color: var(–primary-color); box-shadow: 0 0 0 2px rgba(0, 74, 153, 0.2); } .helper-text { font-size: 0.85em; color: #666; } .error-message { color: #dc3545; font-size: 0.85em; margin-top: 5px; display: none; /* Hidden by default */ } .button-group { display: flex; gap: 10px; margin-top: 20px; flex-wrap: wrap; } .btn { padding: 10px 20px; border: none; border-radius: 5px; cursor: pointer; font-size: 1rem; font-weight: bold; transition: background-color 0.3s ease; text-decoration: none; display: inline-block; } .btn-primary { background-color: var(–primary-color); color: white; } .btn-primary:hover { background-color: #003366; } .btn-success { background-color: var(–success-color); color: white; } .btn-success:hover { background-color: #218838; } .btn-secondary { background-color: #6c757d; color: white; } .btn-secondary:hover { background-color: #5a6268; } #results { margin-top: 25px; padding: 20px; background-color: var(–primary-color); color: white; border-radius: 8px; text-align: center; box-shadow: 0 4px 10px rgba(0, 74, 153, 0.3); } #results h3 { color: white; margin-top: 0; margin-bottom: 15px; } .result-item { margin-bottom: 10px; font-size: 1.1em; } .result-item strong { color: #cce5ff; } .primary-result { font-size: 2em; font-weight: bold; margin-top: 15px; color: #fff; padding: 10px; border-radius: 5px; display: inline-block; background-color: var(–success-color); } .formula-explanation { font-size: 0.9em; color: #eee; margin-top: 15px; font-style: italic; } table { width: 100%; border-collapse: collapse; margin-top: 20px; margin-bottom: 20px; box-shadow: 0 2px 5px var(–shadow-color); } th, td { padding: 12px; text-align: left; border: 1px solid var(–border-color); } thead { background-color: var(–primary-color); color: white; } tbody tr:nth-child(even) { background-color: #f2f2f2; } caption { font-size: 1.1em; font-weight: bold; color: var(–primary-color); margin-bottom: 10px; text-align: left; } canvas { display: block; margin: 20px auto; background-color: var(–card-background); border-radius: 5px; box-shadow: 0 2px 5px var(–shadow-color); } .article-content { margin-top: 40px; background-color: var(–card-background); padding: 30px; border-radius: 8px; box-shadow: 0 4px 15px var(–shadow-color); } .article-content p, .article-content ul, .article-content ol { margin-bottom: 15px; } .article-content li { margin-bottom: 8px; } .article-content a { color: var(–primary-color); text-decoration: none; } .article-content a:hover { text-decoration: underline; } .faq-item { margin-bottom: 15px; padding-bottom: 10px; border-bottom: 1px dashed var(–border-color); } .faq-item:last-child { border-bottom: none; } .faq-item strong { display: block; color: var(–primary-color); margin-bottom: 5px; } .internal-links-section ul { list-style: none; padding: 0; } .internal-links-section li { margin-bottom: 15px; } .internal-links-section a { font-weight: bold; } .internal-links-section span { font-size: 0.9em; color: #666; display: block; margin-top: 3px; } @media (min-width: 768px) { .container { margin: 30px auto; } .loan-calc-container { flex-direction: row; flex-wrap: wrap; justify-content: space-between; } .loan-calc-container .input-group { width: calc(50% – 10px); /* Two columns for inputs */ } .button-group { justify-content: flex-start; } } @media (min-width: 992px) { .loan-calc-container .input-group { width: calc(33.333% – 15px); /* Three columns for inputs */ } }

Superheat Calculator

Calculate and understand refrigerant superheat for optimal HVAC system performance.

Superheat Calculator

Temperature of the liquid refrigerant before the expansion device.
The boiling point of the refrigerant in the evaporator coil.
Temperature of the refrigerant vapor leaving the evaporator.

Calculation Results

Superheat (°F):
Evaporator Temperature Difference (°F):
Liquid Line Temperature (°F):
Suction Line Temperature (°F):
Superheat is calculated as: Suction Line Temperature – Evaporator Saturation Temperature. Evaporator Temperature Difference (ETD) is calculated as: Evaporator Saturation Temperature – Liquid Line Temperature.

Superheat Trend Analysis

Input Data Table

Parameter Value Unit
Liquid Line Temperature °F
Evaporator Saturation Temperature °F
Suction Line Temperature °F

What is Superheat?

Superheat is a critical concept in refrigeration and air conditioning systems. It refers to the amount of heat absorbed by a refrigerant vapor *after* it has completely boiled (vaporized) within the evaporator coil. In simpler terms, it's the temperature increase of the refrigerant vapor above its saturation temperature (boiling point) as it travels through the suction line towards the compressor. Understanding and accurately calculating superheat is fundamental for diagnosing system performance, identifying potential issues, and ensuring efficient operation.

Who should use it: HVAC technicians, refrigeration engineers, system designers, and anyone involved in the maintenance, repair, or installation of air conditioning and refrigeration equipment will find superheat calculations indispensable. It's a primary diagnostic tool for assessing the charge level and the performance of the metering device (like a TXV or capillary tube).

Common misconceptions: A frequent misunderstanding is that superheat is the same as subcooling. Subcooling relates to the liquid line temperature *before* the metering device, while superheat relates to the vapor line temperature *after* the evaporator. Another misconception is that higher superheat is always better; in reality, there's an optimal range, and both too high and too low superheat indicate problems.

Superheat Formula and Mathematical Explanation

Calculating superheat is a straightforward process that involves measuring temperatures at specific points in the refrigeration cycle. The core formula is based on the principle that the refrigerant leaving the evaporator should be entirely in a vapor state and slightly warmer than its boiling point to ensure no liquid refrigerant reaches the compressor.

The primary calculation for superheat is:

Superheat (°F) = Suction Line Temperature (°F) – Evaporator Saturation Temperature (°F)

To further diagnose system performance, we also calculate the Evaporator Temperature Difference (ETD), which helps assess the metering device's function and the overall heat transfer efficiency of the evaporator.

Evaporator Temperature Difference (ETD) (°F) = Evaporator Saturation Temperature (°F) – Liquid Line Temperature (°F)

Variable Explanations:

Superheat Calculation Variables
Variable Meaning Unit Typical Range
Suction Line Temperature The measured temperature of the refrigerant vapor in the suction line, typically near the compressor inlet. °F Varies widely based on system load and refrigerant type, but generally above evaporator saturation temp.
Evaporator Saturation Temperature The temperature at which the refrigerant boils and changes from liquid to vapor within the evaporator coil. This is determined by the low-side pressure. °F Typically 30-50°F for AC systems, lower for freezers.
Liquid Line Temperature The measured temperature of the refrigerant liquid in the liquid line, typically before the metering device. °F Usually slightly below ambient, but significantly higher than evaporator saturation temp.
Superheat The temperature increase of the refrigerant vapor above its saturation point after leaving the evaporator. °F Typically 8-20°F for TXV systems, 10-30°F for fixed orifice systems (varies by manufacturer and application).
Evaporator Temperature Difference (ETD) The difference between the liquid line temperature and the evaporator saturation temperature. Indicates how much heat the liquid refrigerant has lost before reaching the metering device. °F Typically 10-20°F.

Practical Examples (Real-World Use Cases)

Accurate superheat calculation is vital for diagnosing common HVAC issues. Here are two practical examples:

Example 1: Low Refrigerant Charge

A homeowner complains their air conditioner isn't cooling effectively. An HVAC technician arrives and takes the following measurements:

  • Liquid Line Temperature: 105°F
  • Evaporator Saturation Temperature: 45°F
  • Suction Line Temperature: 55°F

Using the calculator (or manual calculation):

  • Superheat = 55°F – 45°F = 10°F
  • ETD = 45°F – 105°F = -60°F

Interpretation: The superheat (10°F) is within a typical range for a TXV system. However, the ETD is significantly negative (-60°F). This indicates that the liquid line temperature is much *higher* than the evaporator saturation temperature, which is impossible. This scenario strongly suggests a low refrigerant charge. The system is starving for refrigerant, causing the evaporator to boil off refrigerant too early, leading to low suction pressure and thus a low evaporator saturation temperature. The low charge prevents proper heat absorption and cooling.

Example 2: Faulty Metering Device (TXV)

Another system is running, but the cooling is inconsistent, and the evaporator coil sometimes freezes. Measurements are taken:

  • Liquid Line Temperature: 95°F
  • Evaporator Saturation Temperature: 40°F
  • Suction Line Temperature: 85°F

Using the calculator:

  • Superheat = 85°F – 40°F = 45°F
  • ETD = 40°F – 95°F = -55°F

Interpretation: The superheat is extremely high (45°F), indicating that the refrigerant vapor is getting significantly overheated after leaving the evaporator. The negative ETD (-55°F) again points to an issue, likely related to the metering device. In this case, a malfunctioning Thermal Expansion Valve (TXV) that is stuck open or not sensing properly could be flooding the evaporator with too much refrigerant. This leads to low suction pressure and a low saturation temperature, but the excessive refrigerant flow might still result in high superheat if the compressor is removing vapor faster than the evaporator can supply it, or if the evaporator is undersized for the load. The freezing issue also points to overfeeding and potential liquid floodback. This high superheat suggests the TXV is not correctly controlling refrigerant flow.

How to Use This Superheat Calculator

Our Superheat Calculator is designed for ease of use by HVAC professionals. Follow these simple steps to get accurate results and diagnostic insights:

  1. Gather Measurements: Using appropriate tools (thermometers, pressure gauges), accurately measure the following three temperatures on the air conditioning or refrigeration system:
    • Liquid Line Temperature: Measure the temperature of the liquid refrigerant line, typically on the high-pressure side, just before the expansion device (TXV, capillary tube, etc.).
    • Evaporator Saturation Temperature: Measure the low-side (suction) pressure and use a refrigerant pressure-temperature chart or slide rule to find the corresponding saturation temperature. This is the boiling point of the refrigerant in the evaporator.
    • Suction Line Temperature: Measure the temperature of the vapor refrigerant line on the low-pressure side, usually near the compressor inlet.
  2. Input Values: Enter the measured temperatures into the corresponding fields in the calculator: "Liquid Line Temperature (°F)", "Evaporator Saturation Temperature (°F)", and "Suction Line Temperature (°F)".
  3. Calculate: Click the "Calculate Superheat" button. The calculator will instantly display the calculated Superheat and the Evaporator Temperature Difference (ETD).
  4. Interpret Results:
    • Superheat: This is your primary diagnostic value. Compare it to the manufacturer's recommended superheat range for the specific system and refrigerant type.
      • Too High Superheat: Often indicates a low refrigerant charge, a restricted metering device (TXV failing to open enough), or low evaporator airflow.
      • Too Low Superheat (or 0°F): Often indicates a high refrigerant charge, a faulty metering device (TXV stuck open), or excessive evaporator load. Liquid refrigerant reaching the compressor is dangerous.
    • ETD: This value helps assess the metering device's performance and heat transfer. A significantly negative ETD usually points to issues with the metering device or refrigerant charge.
  5. Analyze Chart and Table: The dynamic chart visualizes the relationship between your measured temperatures and the calculated superheat/ETD. The table summarizes your input data for easy reference.
  6. Reset or Copy: Use the "Reset" button to clear the fields and start over. Use the "Copy Results" button to save or share your findings.

Remember, these calculations are diagnostic tools. Always consult the equipment manufacturer's service manual for specific operating parameters and troubleshooting procedures. Proper HVAC system maintenance is key.

Key Factors That Affect Superheat Results

Several environmental and system-specific factors influence the superheat readings and their interpretation. Understanding these is crucial for accurate diagnosis:

  1. Refrigerant Type: Different refrigerants have distinct pressure-temperature characteristics. The saturation temperature corresponding to a given pressure varies significantly between refrigerants like R-410A, R-22, or R-134a. Always use the correct P-T chart for the refrigerant being serviced.
  2. System Load: The amount of heat the evaporator needs to absorb directly impacts superheat. On a very hot day with high cooling demand, the evaporator will absorb more heat, potentially leading to higher superheat if the metering device responds correctly. Conversely, low load conditions can result in lower superheat.
  3. Metering Device Type:
    • Thermostatic Expansion Valves (TXVs): Designed to maintain a relatively constant superheat. They adjust refrigerant flow based on the suction line temperature sensed by a bulb.
    • Fixed Orifice (Capillary Tube): These devices have a fixed restriction. Superheat will fluctuate more significantly with system load and charge variations.
    Manufacturer specifications will provide target superheat ranges specific to the metering device type.
  4. Refrigerant Charge Level: This is one of the most common culprits for incorrect superheat.
    • Low Charge: Leads to reduced refrigerant flow, lower evaporator pressure/temperature, and typically higher superheat. The system may struggle to absorb enough heat.
    • High Charge: Can lead to overfeeding of the evaporator, lower superheat (potentially liquid floodback), and higher head pressure.
    Accurate refrigerant charge calculation is essential.
  5. Airflow Across the Evaporator Coil: Insufficient airflow (due to dirty filters, blocked vents, or fan issues) reduces the rate of heat transfer into the refrigerant. This can cause the refrigerant to boil off too quickly, leading to low suction pressure and potentially low superheat, or even evaporator coil freezing.
  6. Suction Line Insulation: The suction line should be insulated to prevent heat gain from the surrounding environment. If the insulation is damaged or missing, ambient heat can artificially raise the suction line temperature, leading to a falsely high superheat reading. Always check insulation integrity.
  7. Liquid Line Restrictions: A restriction before the metering device (e.g., clogged filter drier) can cause a significant pressure drop, leading to flashing of liquid refrigerant into vapor before it reaches the expansion device. This can affect both ETD and superheat readings.

Frequently Asked Questions (FAQ)

Q1: What is the ideal superheat for an air conditioning system?

A: The ideal superheat varies by manufacturer and system type. For systems with a TXV, it's typically between 8°F and 20°F. For fixed orifice systems, it might be higher, often 10°F to 30°F. Always refer to the manufacturer's specifications for the specific equipment.

Q2: Can superheat be too low? What does it mean?

A: Yes, superheat can be too low. A superheat reading of 0°F or very close to it indicates that the refrigerant is leaving the evaporator as a saturated vapor or, worse, as a liquid-vapor mix. This is dangerous as liquid refrigerant can wash out oil from the compressor, leading to catastrophic failure. It often signifies an overcharged system or a TXV stuck open.

Q3: How does a low refrigerant charge affect superheat?

A: A low refrigerant charge typically causes superheat to increase. With less refrigerant in the system, the evaporator cannot absorb heat efficiently, leading to lower suction pressure and saturation temperature. The refrigerant boils off earlier in the evaporator, and the remaining vapor absorbs more heat as it travels to the compressor, increasing superheat.

Q4: What is the difference between superheat and subcooling?

A: Superheat measures the temperature increase of refrigerant vapor *above* its saturation point after it leaves the evaporator. Subcooling measures the temperature decrease of refrigerant liquid *below* its saturation point in the liquid line, *before* the metering device. Both are crucial diagnostic indicators, but they relate to different parts of the refrigeration cycle.

Q5: How do I measure Evaporator Saturation Temperature accurately?

A: You measure the low-side (suction) pressure at the service valve near the compressor. Then, using a refrigerant pressure-temperature (P-T) chart or a digital manifold gauge that does this calculation for you, you find the saturation temperature that corresponds to that measured pressure for the specific refrigerant type (e.g., R-410A).

Q6: Does ambient temperature affect superheat readings?

A: Yes, indirectly. Ambient temperature affects the cooling load on the system. Higher ambient temperatures mean higher cooling demand, which can lead to higher evaporator temperatures and potentially higher superheat if the system is operating correctly. It also affects the liquid line temperature.

Q7: What if my system uses a fixed orifice instead of a TXV?

A: Systems with fixed orifices (like capillary tubes) generally have wider superheat ranges and are more sensitive to refrigerant charge. The target superheat values will differ from TXV systems. It's essential to consult the manufacturer's data for fixed orifice systems, as they often require charging by weight or specific superheat targets under defined operating conditions.

Q8: Can I use this calculator for commercial refrigeration systems?

A: Yes, the fundamental principles of superheat calculation apply to most refrigeration systems, including commercial ones. However, target superheat ranges and operating conditions can vary significantly based on the application (e.g., walk-in freezers vs. display cases). Always prioritize manufacturer specifications for commercial equipment.

© 2023 Your Company Name. All rights reserved.

var liquidTempInput = document.getElementById('liquidTemp'); var evapTempInput = document.getElementById('evapTemp'); var suctionTempInput = document.getElementById('suctionTemp'); var liquidTempError = document.getElementById('liquidTempError'); var evapTempError = document.getElementById('evapTempError'); var suctionTempError = document.getElementById('suctionTempError'); var superheatResultSpan = document.getElementById('superheatResult'); var evapTempDiffResultSpan = document.getElementById('evapTempDiffResult'); var liquidLineTempResultSpan = document.getElementById('liquidLineTempResult'); var suctionLineTempResultSpan = document.getElementById('suctionLineTempResult'); var tableLiquidTemp = document.getElementById('tableLiquidTemp'); var tableEvapTemp = document.getElementById('tableEvapTemp'); var tableSuctionTemp = document.getElementById('tableSuctionTemp'); var chart; var chartData = { labels: [], datasets: [{ label: 'Superheat (°F)', data: [], borderColor: 'var(–primary-color)', fill: false, tension: 0.1 }, { label: 'Evaporator Temp Difference (°F)', data: [], borderColor: 'var(–success-color)', fill: false, tension: 0.1 }] }; function validateInput(inputElement, errorElement, label, minValue, maxValue) { var value = parseFloat(inputElement.value); var isValid = true; errorElement.style.display = 'none'; inputElement.style.borderColor = 'var(–border-color)'; if (isNaN(value)) { errorElement.textContent = label + ' is required.'; errorElement.style.display = 'block'; inputElement.style.borderColor = '#dc3545'; isValid = false; } else if (value maxValue) { errorElement.textContent = label + ' cannot be greater than ' + maxValue + '.'; errorElement.style.display = 'block'; inputElement.style.borderColor = '#dc3545'; isValid = false; } return isValid; } function calculateSuperheat() { var liquidTemp = parseFloat(liquidTempInput.value); var evapTemp = parseFloat(evapTempInput.value); var suctionTemp = parseFloat(suctionTempInput.value); var isValid = true; if (!validateInput(liquidTempInput, liquidTempError, 'Liquid Line Temperature', -50, 200)) isValid = false; if (!validateInput(evapTempInput, evapTempError, 'Evaporator Saturation Temperature', -50, 100)) isValid = false; if (!validateInput(suctionTempInput, suctionTempError, 'Suction Line Temperature', -50, 150)) isValid = false; if (!isValid) { superheatResultSpan.textContent = 'Error'; evapTempDiffResultSpan.textContent = 'Error'; liquidLineTempResultSpan.textContent = 'Error'; suctionLineTempResultSpan.textContent = 'Error'; return; } var superheat = suctionTemp – evapTemp; var evapTempDiff = evapTemp – liquidTemp; superheatResultSpan.textContent = superheat.toFixed(1); evapTempDiffResultSpan.textContent = evapTempDiff.toFixed(1); liquidLineTempResultSpan.textContent = liquidTemp.toFixed(1); suctionLineTempResultSpan.textContent = suctionTemp.toFixed(1); tableLiquidTemp.textContent = liquidTemp.toFixed(1); tableEvapTemp.textContent = evapTemp.toFixed(1); tableSuctionTemp.textContent = suctionTemp.toFixed(1); updateChart(superheat, evapTempDiff); } function resetCalculator() { liquidTempInput.value = 90; evapTempInput.value = 40; suctionTempInput.value = 65; liquidTempError.style.display = 'none'; evapTempError.style.display = 'none'; suctionTempError.style.display = 'none'; liquidTempInput.style.borderColor = 'var(–border-color)'; evapTempInput.style.borderColor = 'var(–border-color)'; suctionTempInput.style.borderColor = 'var(–border-color)'; superheatResultSpan.textContent = '–'; evapTempDiffResultSpan.textContent = '–'; liquidLineTempResultSpan.textContent = '–'; suctionLineTempResultSpan.textContent = '–'; tableLiquidTemp.textContent = '–'; tableEvapTemp.textContent = '–'; tableSuctionTemp.textContent = '–'; if (chart) { chart.destroy(); chart = null; } chartData.labels = []; chartData.datasets[0].data = []; chartData.datasets[1].data = []; var canvas = document.getElementById('superheatChart'); var ctx = canvas.getContext('2d'); ctx.clearRect(0, 0, canvas.width, canvas.height); document.getElementById('chartLegend').innerHTML = "; } function updateChart(superheat, evapTempDiff) { var timestamp = new Date().toLocaleTimeString(); chartData.labels.push(timestamp); chartData.datasets[0].data.push(superheat); chartData.datasets[1].data.push(evapTempDiff); // Limit data points to prevent performance issues and keep chart readable var maxDataPoints = 15; if (chartData.labels.length > maxDataPoints) { chartData.labels.shift(); chartData.datasets[0].data.shift(); chartData.datasets[1].data.shift(); } var canvas = document.getElementById('superheatChart'); var ctx = canvas.getContext('2d'); if (chart) { chart.destroy(); } chart = new Chart(ctx, { type: 'line', data: chartData, options: { responsive: true, maintainAspectRatio: false, scales: { x: { title: { display: true, text: 'Time' } }, y: { title: { display: true, text: 'Temperature (°F)' }, beginAtZero: false } }, plugins: { legend: { display: true, position: 'top', }, title: { display: true, text: 'Superheat and ETD Over Time' } } } }); updateChartLegend(); } function updateChartLegend() { var legendHtml = '
'; legendHtml += ' Superheat (°F)'; legendHtml += ' Evaporator Temp Difference (°F)'; legendHtml += '
'; document.getElementById('chartLegend').innerHTML = legendHtml; } function copyResults() { var liquidTemp = parseFloat(liquidTempInput.value); var evapTemp = parseFloat(evapTempInput.value); var suctionTemp = parseFloat(suctionTempInput.value); var superheat = parseFloat(superheatResultSpan.textContent); var evapTempDiff = parseFloat(evapTempDiffResultSpan.textContent); var resultsText = "— Superheat Calculation Results —\n\n"; resultsText += "Inputs:\n"; resultsText += "- Liquid Line Temperature: " + liquidTemp.toFixed(1) + " °F\n"; resultsText += "- Evaporator Saturation Temperature: " + evapTemp.toFixed(1) + " °F\n"; resultsText += "- Suction Line Temperature: " + suctionTemp.toFixed(1) + " °F\n\n"; resultsText += "Outputs:\n"; resultsText += "Superheat: " + (isNaN(superheat) ? "N/A" : superheat.toFixed(1) + " °F") + "\n"; resultsText += "Evaporator Temperature Difference (ETD): " + (isNaN(evapTempDiff) ? "N/A" : evapTempDiff.toFixed(1) + " °F") + "\n\n"; resultsText += "Key Assumptions:\n"; resultsText += "- System is properly charged (unless charge is the diagnostic focus).\n"; resultsText += "- Evaporator airflow is adequate.\n"; resultsText += "- Suction line is properly insulated.\n"; resultsText += "- Refrigerant type is correctly identified for P-T chart usage.\n"; var textArea = document.createElement("textarea"); textArea.value = resultsText; document.body.appendChild(textArea); textArea.select(); try { document.execCommand("copy"); alert("Results copied to clipboard!"); } catch (err) { console.error("Failed to copy results: ", err); alert("Failed to copy results. Please copy manually."); } textArea.remove(); } // Initial calculation on load document.addEventListener('DOMContentLoaded', function() { calculateSuperheat(); var canvas = document.getElementById('superheatChart'); canvas.width = canvas.offsetWidth; // Set canvas width to its container width canvas.height = 300; // Set a fixed height for the chart updateChartLegend(); // Initialize legend }); // Re-calculate on input change liquidTempInput.addEventListener('input', calculateSuperheat); evapTempInput.addEventListener('input', calculateSuperheat); suctionTempInput.addEventListener('input', calculateSuperheat); // Add Chart.js library dynamically if not present (for demonstration, usually included in head) if (typeof Chart === 'undefined') { var script = document.createElement('script'); script.src = 'https://cdn.jsdelivr.net/npm/chart.js@3.7.0/dist/chart.min.js'; script.onload = function() { console.log('Chart.js loaded.'); // Re-run initial calculation after chart library is loaded calculateSuperheat(); }; document.head.appendChild(script); } else { // If Chart.js is already loaded, ensure initial calculation runs calculateSuperheat(); }